Electronic controls   61 SERIES

                                                                                                      H6102




        Dip-Switch setup
        As you can see in the table below, the dither frequency can
        be  fixed  from  80Hz  to  220Hz.  Dip  switch  1-2-3  fixes  the
        various frequency.
             1            2             3        Freq dither
           OFF           OFF          OFF          80Hz
            ON           OFF          OFF          90Hz
           OFF           ON           OFF          100Hz
            ON           ON           OFF          110Hz
           OFF           OFF           ON          120HZ
            ON           OFF           ON          140Hz
           OFF           ON            ON          160Hz
            ON           ON            ON          180Hz
        Dip-switch 4 fixes the the dither level percentage.
           DIP4        % dither
           OFF           MAX
            ON           MIN
        Dip-switch 6-7-8-12 setup the reference input type and the functionality of the input PIN 2.
           DIP6          DIP7         DIP8         DIP12          Reference input           PIN 2      See image
           OFF           OFF          OFF           OFF         0-5V or potentiometer    OUT selector    DIAG 1
           OFF           OFF           ON           OFF                0-10V             OUT selector    DIAG 2
            ON           OFF          OFF           OFF               0-20mA             OUT selector    DIAG 3
           OFF           ON           OFF           ON               +5V 0 –5V           OUT enable      DIAG 4






























        Working
        Once you have ended the above setup, the system is ready to control the valves.
        Giving a set point to the input (~200mV when you use the potentiometer) the current flows to the solenoid starting from
        the minimum current, fixed with the trimmer I MIN, to the maximum current, fixed with the trimmer I MAX, when the set
        point is at maximum value.
        Of course the current to the valves will rise or fall with the time imposed by the ramps, if you disabled the ramps, the
        current will change immediately.