Page 560 - Hydrover-hydraulic-integrated-circuits-catalogue
P. 560
Electronic controls 61 SERIES
H6102
Dip-Switch setup
As you can see in the table below, the dither frequency can
be fixed from 80Hz to 220Hz. Dip switch 1-2-3 fixes the
various frequency.
1 2 3 Freq dither
OFF OFF OFF 80Hz
ON OFF OFF 90Hz
OFF ON OFF 100Hz
ON ON OFF 110Hz
OFF OFF ON 120HZ
ON OFF ON 140Hz
OFF ON ON 160Hz
ON ON ON 180Hz
Dip-switch 4 fixes the the dither level percentage.
DIP4 % dither
OFF MAX
ON MIN
Dip-switch 6-7-8-12 setup the reference input type and the functionality of the input PIN 2.
DIP6 DIP7 DIP8 DIP12 Reference input PIN 2 See image
OFF OFF OFF OFF 0-5V or potentiometer OUT selector DIAG 1
OFF OFF ON OFF 0-10V OUT selector DIAG 2
ON OFF OFF OFF 0-20mA OUT selector DIAG 3
OFF ON OFF ON +5V 0 –5V OUT enable DIAG 4
Working
Once you have ended the above setup, the system is ready to control the valves.
Giving a set point to the input (~200mV when you use the potentiometer) the current flows to the solenoid starting from
the minimum current, fixed with the trimmer I MIN, to the maximum current, fixed with the trimmer I MAX, when the set
point is at maximum value.
Of course the current to the valves will rise or fall with the time imposed by the ramps, if you disabled the ramps, the
current will change immediately.
560 General catalogue September 2023 edition